GasTest Log runs the pressure test on your iPhone: the code preset sets the pressure and the hold, the timer runs on the wall clock, and the start and end gauge photos end up on a one-page PASS/FAIL certificate you can hand to the inspector before you leave.
No paperwork afterwards. The report is finished when the hold is.
These are the base IFGC and IRC defaults the app ships with. They are a starting point, not a ruling: your local amendments win.
| What | Default |
|---|---|
| Test pressure | 3 psi1.5× the working pressure, and never below 3 psi — IFGC 2021 §406.4.1 |
| Hold time | 10 minOnly for a single-family dwelling or a system under 10 ft³. Bigger systems hold half an hour per 500 ft³ — IFGC 2021 §406.4.2 · IRC §G2417.4 |
| Test medium | Air, N₂, CO₂The code lists air, nitrogen, carbon dioxide or an inert gas, and forbids oxygen — IFGC 2021 §406.2 · IRC §G2417.2 |
| Gauge | ≤ 5× scaleA manometer, or a dial gauge whose top of scale is no more than 5× the test pressure — IFGC §406.4 |
Confirm with your AHJ. Jurisdictions amend these numbers, and some utilities ask for a higher pressure or a longer hold than the model code. The app says the same thing on the test screen — check first, then pump up.
Yes. The hold is measured against the wall clock, so locking the screen or leaving the app does not lose time.
Yes. If the gauge drops you can end the hold immediately and the certificate records a FAIL with the time it happened.
The certificate is your record of the test: pressure, hold, both gauge photos and the code section. Whether a jurisdiction accepts a photographed record instead of a witnessed test is up to that jurisdiction — ask your inspector before the appointment.
Yes, the test and the certificate are produced on the phone.