In Britain the test that proves a domestic installation is sound is a tightness test, run to IGEM/UP/1B. It is a different animal from the American pressure test: about a tenth of the pressure, four minutes on the clock instead of ten, and the gas itself in the pipe. Here is the procedure as it stands — and the change that lands on 1 October 2026.
IGEM/UP/1B Edition 4 was published in March 2026. Editions 3 and 4 have run side by side since; Edition 3 is withdrawn on 30 September 2026, and from 1 October every tightness test is to be carried out to Edition 4. The procedure is broadly the same. What changed is how a drop on the gauge is judged:
"Updated tightness testing standard: what you need to know" and "Industry Standard Update 133 (Edition 2)", Registered Gas Engineer, 2026
Smell of gas overrides the gauge. Permissible limits only apply where there are existing appliances and no smell of gas has been reported. A pass with a smell of gas is not a pass.
The permissible-drop figures themselves are in IGEM/UP/1B Edition 4 and are not reproduced here. Read them from the standard, not from a table on somebody's website — including this one.
The two are often searched for as if they were the same thing. They are not built for the same job: the UK test checks a domestic installation at close to the pressure it runs at, with the gas in it; the US test proves new piping before any gas is allowed in.
| UK tightness test | US pressure test | |
|---|---|---|
| Pressure | 20–21 mbar≈ 0.3 psi, natural gas | ≥ 3 psi≈ 207 mbar, or 1.5× working |
| In the pipe | The gas supply, through the meter | Air, nitrogen or CO₂ — never the fuel gasIFGC 2021 §406.2 |
| Timing | 1 + 1 + 2 minlet-by, stabilise, test | 10 mina house; ½ h per 500 ft³ otherwise |
| Who | A Gas Safe registered engineer — required by the Gas Safety (Installation and Use) Regulations 1998 | A licensed plumber or gas fitter, under state and local rules |
The US side in detail: gas pressure test requirements, and what US utilities ask for on paper: pressure test forms.
GasTest Log is built around the American test: its presets, its hold rules and the code sections printed on its certificate are IFGC, IRC and UPC. It does not run the IGEM/UP/1B sequence and its certificate is not a UK gas safety record, so in Britain use the paperwork your Gas Safe registration requires. If you work on both sides of the Atlantic, the US pressure test is the one it is for.
A summary of published guidance on IGEM/UP/1B, not a copy of the standard or a substitute for it. Gas work in Great Britain must be carried out by a Gas Safe registered engineer; work to the standard itself and to your training.
Last reviewed 22 September 2026